HT & LT (Combined) Radiator For JENBACHER JGS420 B25-Radiator
This is a dual-circuit dry cooler (remote radiator) engineered for the Jenbacher JGS420 B25 (20-cylinder, 1540 kW) gas genset. It integrates HT (jacket water) and LT (aftercooler) heat rejection into a single unit, ideal for indoor/containerized installations.
Engine & Heat Load Basics
Model: Jenbacher JGS420 B25 (J420GS-B25)
Rated power: 1540 kW (prime),50 Hz
Fuel: Natural gas, biogas, landfill gas
Cooling loops: HT (jacket) + LT (charge air)
Total heat rejection: ~2.1 MW
HT Loop: ~1300 kW (90°C in / 82°C out)
LT Loop: ~800 kW (45°C in / 62°C out)
Core Design Specs (Combined HT/LT)
Type: Dual-circuit, single-frame dry cooler (no water spray)
Coil: Cu tube + Al fin (standard); epoxy-coated fins (coastal)
Fans: 5–6 axial fans, VFD-controlled, IP55 (380/400 VAC)
Design ambient: 45°C (standard) / 50°C (high ambient)
Design pressure: 1.6 MPa (HT) / 1.0 MPa (LT)
Connections:
HT: DN250 flanged
LT: DN200 flanged
Frame: Hot-dip galvanized steel (Z275)
Dimensions (L×W×H): ~4.2 × 2.1 × 2.5 m
Weight: ~850–1000 kg
Applications
Industrial CHP: Factories, hospitals, hotels (1.5 MW power + heat)
Biogas plants: Landfill, wastewater, agricultural biogas
Containerized gensets: Mobile/remote power (mines, oil/gas)
High ambient regions: Middle East, Southeast Asia (45°C+)
Noise-sensitive areas: Urban, residential zones