V Type HT‑LT Dry Cooling Unit Remote Radiator For MTU 12 V 4000M93 Engine

Engine: MTU 12V4000M93 high‑power diesel engine, prime power ~2340 kW @2100 rpm
Application: Heavy‑duty diesel genset, continuous base‑load power plant, containerized power station
Cooling solution: V‑shape dual‑circuit remote dry‑cooling radiator, fully independent HT & LT closed glycol‑water cooling loops, remote heat rejection outside engine room
Working condition: 24/7 continuous operation, high ambient temperature, outdoor installation


Dual‑Circuit Cooling Parameters
HT Circuit (Jacket Water Cooling)
Function: Cool cylinder liner, cylinder head jacket water
Typical temperature range: Supply 85‑95 °C / Return 75‑85 °C
Duty: Dissipate main engine jacket waste heat, stabilize engine thermal state, reduce thermal‑cycle stress
LT Circuit (Charge‑air & Lube‑oil Cooling)
Function: Cool turbo charge‑air intercooler and lube‑oil heat exchanger
Typical temperature range: Supply 32‑40 °C / Return 42‑55 °C
Duty: Precise intake‑air temperature control, guarantee full‑power output, protect turbo and lube‑oil service life

 

V type HTLT Dry Cooling Unit Remote Radiator for MTU 12 V 4000M93 Engine

You Might Also Like

Send Inquiry